YRL7-63&YRL7-63Pro miniature AC circuit breakers are used for home installation, as well as commercial and industrial power distribution systems, providing short-circuit current protection and overload current protection functions.
Summary:
| Modell | YRL7-63 6KA | YRL7-63Por10KA |
| Elektrische Funktionen |
| |
| Nennstrom In | 1,2,3,6,10,16,20,25,32,40,50,63,80,100A | |
| Polen | 1P,1P+N,2P,3P,3P+N,4P | |
| Bemessungsspannung Ue | 230/400V~ | 240/415V- |
| Isolationsspannung Ui | 500V | |
| Nennfrequenz | 50/60 Hz | |
| Bewertetes Ausschaltvermögen | 6.000 A | 10,000A |
| Energiebegrenzende Klasse | 3 | |
| Rated impulse withstand volt age (1.5/50) Uimp | 4.000 V | |
| Dielectric test voltage at ind. Freq, for 1 min | 2kV | |
| Verschmutzungsgrad | 2 | |
| Thermal-magnetic release characteristic | B,C,D | |
| Mechanical Features |
| |
| Elektrisches Leben | 8,000 Cycles | |
| Mechanisches Leben | 20,000 Cycles | |
| Kontaktpositionsanzeige | Ja | |
| Schutzgrad | IP20 | |
| Referenztemperatur für die Einstellung des Thermoelements | 30°C | |
| Ambient temperature(with daily average<35°C) | ・5°C~+40°C | |
| Lagertemperatur | ・25°C~+70°C | |
Summary:
| Modell | YRL7-63 6KA YRL7-63Por |
| Installation |
|
| Terminalverbindungstyp | Cable/Pin-type busbar/U-type busbar |
| Klemmengröße oben/unten für Kabel | 25 mm2 18-3 AWG |
| Klemmengröße oben/unten für Sammelschiene | 25 mm2 18-3 AWG |
| Anzugsdrehmoment | 2.5Nm 22in-lbs |
| Montage | On DIN rail EN60715(35mm)by means of fast clip device |
| Verbindung | Von oben und unten |
| Kombination mit Zubehör |
|
| Hilfskontakt | VON |
| Alarmkontakt | FB |
| Arbeitsstromauslöser | MX |
| Over/Under voltage release | MV+MN |
Circuit diagram: